Box fill & pull-box sizing
Add each applicable fill allowance or check minimum pull-box dimensions. The calculation uses fixed NEC 2026 reference data; a project’s selected edition remains separate.
Within selected box volume
0.75 in³ remaining.
- Required volume
- 20.25 in³
- Selected box volume
- 21.00 in³
- Remaining volume
- 0.75 in³
Allowance breakdown
- 13.50 in³
Conductors and qualifying long loops 314.16(B)(1)
6 × 12 AWG at 2.25 in³
- 4.50 in³
Device yokes / straps 314.16(B)(4)
1 yoke(s) × 2 × 12 AWG allowance (2.25 in³)
- 2.25 in³
Equipment grounding / bonding conductors 314.16(B)(5)
1 conductor(s): 1 allowance for the first four + ¼ allowance for each additional conductor, based on 12 AWG (2.25 in³)
21.00 in³ listed volume (Table 314.16(A))
Box fill: 314.16(A), Table 314.16(A), 314.16(B)(1)–(6), and Table 314.16(B)(4). Pull boxes: 314.28(A)(1)–(2). A project’s selected NEC edition is shown as project context and does not change this fixed 2026 data set.