Raceway fill calculator

Check repeated THHN / THWN-2 conductors against an EMT, RMC, PVC Schedule 40, or PVC Schedule 80 trade size. The permitted fill changes with conductor count.

Calculation inputs

Conductor run

Enter a whole number from 1 to 1,000.

This calculator models repeated conductors of one selected size in one selected raceway.

Raceway result

3/4″ EMT · 3 × 12 AWG
Fill is within the selected limitLimit · 40%
Total conductor area
0.0399 in²

3 × 0.0133 in² per conductor

Allowable conductor area
0.2132 in²

40% of 0.5330 in² EMT area

Calculated fill percentage
7.5%

Total conductor area ÷ selected raceway internal area × 100

NEC references

Chapter 9, Table 1 (permitted fill); Table 4 (EMT raceway area); Table 5 (THHN / THWN-2 conductor area); Article 358 (EMT).

Edition check required

Reference values use NFPA 70 (NEC) 2026. Verify the edition adopted by your jurisdiction and any local amendments. This reference tool does not replace project review or AHJ requirements.